Pulverized Coal Mill Outlet (PA) Flow Control — Control Design
Shared by TSIMEREZIVO Team · 4 Oct 2026 · 54 views
# TSIMEREZIVO Template: Pulverized Coal Mill Outlet (PA) Flow Control
**Category:** Power Plant | **Industry:** Thermal Power Generation | **Language:** Ladder / Structured Text
---
## 📋 Overview
### Purpose
Regulate primary air (PA) flow and temperature from the coal mill to maintain consistent coal-in-air concentration (fuel feed) to the furnace. The mill grinds raw coal into powder (~200 µm), mixes with hot air to fluidize particles, and transports coal-air suspension to burners. Control objectives: prevent accumulation (blockage), maintain temperature (too cold = moisture condensation), match burner demand.
### Typical Application
- **Plant:** 100–300 MWe coal-fired boiler
- **Coal Mill:** Ball or bowl mill (impact grinding)
- **Primary Air Inlet:** 120–180°C (recycled flue gas + duct heater mix)
- **PA Flow:** 40–100 kg/s (varies with load)
- **Mill Outlet Temp:** 65–85°C (coal + air mixture)
- **Coal Fineness:** 200 mesh (76 µm); measured by Blaine value (~2500 cm²/g typical)
### Critical Balance
- **Too much PA:** Coal particles blow past burners into furnace (escape combustion); CO spikes
- **Too little PA:** Coal accumulates in mill → blockage → conveying line rupture
- **Too cool:** Moisture in coal condenses → bridging (powder clogs) → shutdown
- **Too hot:** Coal particles devolatize prematurely → flame stability loss
---
## 🎯 Control Philosophy
### Key Equations
**Coal Mass Flow (Indirect Measurement):**
```
Coal Flow [kg/s] ≈ PA Flow [kg/s] × Coal Concentration [%] / (100 − Coal %)
Typical: 60 kg/s PA × (25% coal) / 75% air = 20 kg/s coal + 40 kg/s air
(stoichiometric balance depends on coal rank)
```
**Mill Outlet Temperature (Psychrometric Balance):**
```
T_outlet [°C] = T_PA_inlet [°C] − ΔT_evaporative_cooling
= T_inlet − (latent heat of moisture evaporation / sensible heat)
≈ 120°C inlet − 35°C = 85°C outlet
If T_outlet < 60°C: Risk of coal moisture condensation → bridging
```
**Coal Fineness (Blaine Value):**
```
Blaine [cm²/g] = specific surface area of particles
<1500 cm²/g → Coarse; poor burnout (CO emissions)
1500-2500 cm²/g → Optimal (this range)
>3000 cm²/g → Fine; ring flash → mill vibration
Scan mill discharge via online Blaine analyzer (slow feedback, 5–10 min response)
```
### Control Strategy: Cascade PA Flow + Temperature
```
Load Demand (MW)
│
├─→ [Load Table] → Desired Coal Flow [kg/s]
│ │
│ ├─→ Coal Conc % (fixed 22–25%)
│ │
│ └─→ Required PA Flow [kg/s]
│ │
│ ├─→ Mill Fan VFD Speed
│ │
│ └─→ PA valve modulation
│
└─→ [Temperature Control] → PA Duct Heater (electric OR steam)
├─→ Maintain 65–85°C outlet
└─→ Prevent condensation
```
---
## 🏗️ Control Logic
### Pseudocode: Coal Mill Outlet PA Control
```pascal
PROGRAM CoalMillOutletControl;
{ ========== DECLARATIONS ========== }
VAR
-- INPUT SENSORS
pa_flow_actual : REAL; { 0-150 kg/s, differential pressure flow meter }
mill_outlet_temp : REAL; { 0-100 °C, RTD in mill discharge }
pa_inlet_temp : REAL; { 0-200 °C, duct heater outlet }
mill_vibration : REAL; { 0-10 mm/s, accelerometer (fineness risk) }
coal_mill_load_amps : REAL; { 0-500 A, motor current (grinding effort) }
mill_bowl_temperat : REAL; { 0-100 °C, optional; mill internals }
burner_demand_signal : REAL; { 0-100 %, from burner assembly }
-- CONTROL SETPOINTS
pa_flow_sp : REAL; { kg/s, load-scheduled }
mill_outlet_temp_sp : REAL := 75.0; { Target °C }
mill_outlet_temp_high : REAL := 85.0; { Risk of coal devolatilization }
mill_outlet_temp_low : REAL := 60.0; { Risk of moisture condensation }
mill_vibration_alarm : REAL := 6.0; { mm/s, ring flash or rough grinding }
-- CONTROL LOOPS
-- Loop 1: PA Flow (Primary)
pa_flow_error : REAL;
pa_flow_integral : REAL := 0.0;
kp_pa_flow : REAL := 0.08;
ki_pa_flow : REAL := 0.005;
-- Loop 2: Temperature (Secondary)
temp_error : REAL;
temp_integral : REAL := 0.0;
kp_temp : REAL := 0.20;
ki_temp : REAL := 0.008;
-- LOAD SCHEDULING
boiler_load_mw : REAL;
coal_demand_table : ARRAY[0..100] OF REAL; { Preloaded: load% → coal kg/s }
pa_flow_from_load : REAL;
-- OUTPUT COMMANDS
mill_fan_vfd_command : REAL; { 0-60 Hz to mill fan drive }
duct_heater_command : REAL; { 0-100 % electric or steam valve }
-- DIAGNOSTICS
coal_fineness_blaine : REAL; { cm²/g (from mill analyzer, slow) }
fineness_trend : REAL; { Rising = fining; falling = coarsening }
mill_health_index : INT; { 0-100; 100 = optimal }
BEGIN
{ ========== LOAD-BASED PA FLOW SCHEDULING ========== }
-- Furnace load determines coal feed demand
-- Table: 0% load → 0 kg/s coal; 100% load → 40 kg/s coal
-- Reverse lookup: coal demand → PA flow requirement
-- Example coal_demand_table:
-- [0] = 0 kg/s @ 0% load
-- [25] = 10 kg/s @ 25% load
-- [50] = 20 kg/s @ 50% load
-- [75] = 30 kg/s @ 75% load
-- [100] = 40 kg/s @ 100% load
coal_demand_kg_s := coal_demand_table[ROUND(boiler_load_mw / 3)]; { Scale load to table index }
{ Assuming coal concentration 25% in PA stream:
PA Flow = Coal Flow / 0.25 = Coal Flow × 4
}
pa_flow_sp := coal_demand_kg_s × 4.0;
{ ========== LOOP 1: PA FLOW CONTROL (Primary) ========== }
pa_flow_error := pa_flow_sp − pa_flow_actual;
-- Proportional term
p_term_flow := kp_pa_flow * pa_flow_error;
-- Integral (slow correction)
pa_flow_integral := pa_flow_integral + (ki_pa_flow * pa_flow_error * scan_time);
IF pa_flow_integral > 0.20 THEN pa_flow_integral := 0.20; END_IF;
IF pa_flow_integral < -0.15 THEN pa_flow_integral := -0.15; END_IF;
-- VFD command (mill fan speed)
mill_fan_vfd_command := 25.0 + (p_term_flow + pa_flow_integral) × 50.0;
IF mill_fan_vfd_command < 10.0 THEN mill_fan_vfd_command := 10.0; END_IF;
IF mill_fan_vfd_command > 60.0 THEN mill_fan_vfd_command := 60.0; END_IF;
{ ========== LOOP 2: MILL OUTLET TEMPERATURE CONTROL (Secondary) ========== }
temp_error := mill_outlet_temp_sp − mill_outlet_temp;
-- Proportional term (duct heater is fast, ~5 sec response)
p_term_temp := kp_temp * temp_error;
-- Integral
temp_integral := temp_integral + (ki_temp * temp_error * scan_time);
IF temp_integral > 0.30 THEN temp_integral := 0.30; END_IF;
IF temp_integral < -0.20 THEN temp_integral := -0.20; END_IF;
-- Duct heater command
duct_heater_command := 40.0 + (p_term_temp + temp_integral) × 60.0;
IF duct_heater_command < 0.0 THEN duct_heater_command := 0.0; END_IF;
IF duct_heater_command > 100.0 THEN duct_heater_command := 100.0; END_IF;
{ ========== MILL HEALTH MONITORING ========== }
-- Check 1: Vibration (fineness risk)
IF mill_vibration > mill_vibration_alarm THEN
{ WARN: "Mill vibration high — possible ring flash or coarse coal" }
-- If vibration persists: reduce mill output flow OR reduce bowl speed
END_IF;
-- Check 2: Motor current trend (grinding effort)
IF coal_mill_load_amps > 400.0 THEN
{ WARN: "Mill motor current high — coal too wet OR bowl wear" }
END_IF;
-- Check 3: Temperature excursion (devolatilization)
IF mill_outlet_temp > mill_outlet_temp_high THEN
{ ALARM: "Mill outlet temp HIGH — coal devolatilizing prematurely" }
{ ACTION: Reduce duct heater; increase PA damper opening }
END_IF;
-- Check 4: Temperature too low (condensation)
IF mill_outlet_temp < mill_outlet_temp_low THEN
{ WARN: "Mill outlet temp low — moisture condensation risk; increase heater" }
END_IF;
-- Check 5: PA flow mismatch (flow meter fault or mill blockage)
IF ABS(pa_flow_actual − pa_flow_sp) > 15.0 THEN
{ WARN: "PA flow mismatch by {value} kg/s — check for mill blockage or meter error" }
END_IF;
{ ========== FINENESS MONITORING (Slow Feedback) ========== }
-- Blaine value from mill analyzer (5–10 min lag)
-- Track trend: increasing = coal getting finer (OK); decreasing = coarser (wear)
IF coal_fineness_blaine < 1500.0 THEN
{ WARN: "Coal fineness LOW (coarse) — burner prep poor; CO may spike" }
mill_health_index := 60;
ELSIF coal_fineness_blaine > 3000.0 THEN
{ WARN: "Coal fineness HIGH (too fine) — ring flash possible; reduce mill" }
mill_health_index := 65;
ELSE
mill_health_index := 95; { Optimal }
END_IF;
{ ========== UPDATE STATE FOR NEXT CYCLE ========== }
pa_flow_prev := pa_flow_actual;
temp_prev := mill_outlet_temp;
{ ========== SEND COMMANDS ========== }
-- Output 1: mill_fan_vfd_command (0-60 Hz to mill fan drive)
-- Output 2: duct_heater_command (0-100 % to electric heater or steam valve)
-- Output 3: mill_health_index (for HMI display)
END_PROGRAM;
```
---
## 🏷️ Tag List
| Tag Name | Type | Range | Units | Description |
|----------|------|-------|-------|-------------|
| `PA_FLOW_ACTUAL` | AI | 0–150 | kg/s | Differential pressure flow meter (Annubar) |
| `MILL_OUTLET_TEMP` | AI | 0–100 | °C | Coal-air mixture temperature (RTD) |
| `PA_INLET_TEMP` | AI | 0–200 | °C | Duct heater outlet temperature |
| `MILL_VIBRATION` | AI | 0–10 | mm/s | Accelerometer (fineness/ring flash indicator) |
| `COAL_MILL_LOAD_AMPS` | AI | 0–500 | A | Motor current (grinding effort) |
| `COAL_FINENESS_BLAINE` | AI | 1000–4000 | cm²/g | Blaine value (from mill analyzer, slow) |
| `MILL_OUTLET_TEMP_SP` | REAL | 60–85 | °C | Setpoint |
| `PA_FLOW_SP` | REAL | 0–150 | kg/s | Load-scheduled setpoint |
| `MILL_FAN_VFD_CMD` | AO | 0–60 | Hz | 0-10 VDC to mill fan drive |
| `DUCT_HEATER_CMD` | AO | 0–100 | % | Electric heater or steam valve command |
---
## 🚨 Alarm & Trip Matrix
| Condition | Threshold | Severity | Action | Recovery |
|-----------|-----------|----------|--------|----------|
| **Temp High** | > 85°C | 🔴 CRIT | Reduce heater; coal may devolatilize | < 75°C |
| **Temp Low** | < 60°C | ⚠️ WARN | Moisture condensation risk; increase heater | > 70°C |
| **PA Flow Low** | <SP−15 kg/s | ⚠️ WARN | Mill blockage or meter fault; boost fan | >SP−5 kg/s |
| **Vibration High** | > 6 mm/s | ⚠️ WARN | Ring flash or coarse product; reduce mill | < 4 mm/s |
| **Motor Amp High** | > 450 A | ⚠️ WARN | Wet coal or bowl wear; reduce load | < 400 A |
| **Fineness Coarse** | < 1500 Blaine | ⚠️ WARN | Poor coal grind; burner prep degraded | > 2000 |
| **Fineness Fine** | > 3000 Blaine | 🔴 CRIT | Ring flash imminent; stop mill | < 2800 |
---
## 📺 HMI Layout
### Coal Mill Outlet Control Panel
```
┌───────────────────────────────────────────────┐
│ COAL MILL OUTLET PA FLOW & TEMP CONTROL │
├───────────────────────────────────────────────┤
│ │
│ ╔═════════════ PA FLOW STATUS ═════════╗ │
│ ║ Actual: 61.2 kg/s ║ │
│ ║ Setpoint: 60.0 kg/s (Load 50%)║ │
│ ║ Error: +1.2 kg/s (good) ║ │
│ ║ Mill Fan: ████████░░ 32 Hz ║ │
│ ╚═════════════════════════════════════════╝ │
│ │
│ ╔═════ TEMPERATURE & MOISTURE ═════╗ │
│ ║ Outlet: 74.5°C ✓ (SP: 75°C) ║ │
│ ║ Inlet: 125°C (Duct heater) ║ │
│ ║ ΔT: 50.5°C ║ │
│ ║ Heater: ███████░░░ 70% ║ │
│ ║ Moisture Risk: LOW ✓ ║ │
│ ╚═════════════════════════════════╝ │
│ │
│ ╔═════════ MILL HEALTH METRICS ════════╗ │
│ ║ Vibration: 2.3 mm/s (Normal) ║ │
│ ║ Motor Amps: 385 A (79% rated) ║ │
│ ║ Fineness: 2350 Blaine (Opt) ║ │
│ ║ Health Index: 95/100 Excellent ║ │
│ ╚═════════════════════════════════════╝ │
│ │
│ ⚠️ [NONE] 🔴 [NONE] │
│ │
│ Load: 50% | Coal: 20 kg/s | Status: Running │
│ │
└───────────────────────────────────────────────┘
```
---
## 🔧 Configuration Parameters
```json
{
"coal_mill_outlet": {
"description": "PA flow + temperature control for coal mill outlet",
"mill_outlet_temp_setpoint_celsius": 75.0,
"scan_time_sec": 2.0,
"pa_flow_control": {
"proportional_gain_kp": 0.08,
"integral_gain_ki": 0.005,
"integral_limit_hi": 0.20,
"integral_limit_lo": -0.15,
"fan_vfd_range_hz": [10.0, 60.0]
},
"temperature_control": {
"proportional_gain_kp": 0.20,
"integral_gain_ki": 0.008,
"integral_limit_hi": 0.30,
"integral_limit_lo": -0.20,
"heater_range_percent": [0, 100]
},
"alarms": {
"temp_high_celsius": 85.0,
"temp_low_celsius": 60.0,
"vibration_alarm_mm_per_sec": 6.0,
"motor_amp_alarm": 450.0,
"fineness_min_blaine": 1500.0,
"fineness_max_blaine": 3000.0
},
"load_scheduling": {
"coal_demand_at_0_percent_load_kg_s": 0.0,
"coal_demand_at_50_percent_load_kg_s": 20.0,
"coal_demand_at_100_percent_load_kg_s": 40.0,
"coal_concentration_percent": 25.0
}
}
}
```
---
## 📝 Implementation Checklist
### Commissioning (3 days)
**Day 1: Hardware Verification**
- [ ] PA flow meter calibrated: 0–150 kg/s ±5% accuracy
- [ ] RTD temps verified: outlet ±2°C, inlet ±2°C
- [ ] Mill fan VFD tested: 10–60 Hz ramp smooth ✓
- [ ] Duct heater response: 0% → 100% → temp rises ~40°C ✓
- [ ] Vibration sensor baseline: normal operation <2 mm/s
**Day 2: Control Loop Commissioning (10% load, low coal flow)**
- [ ] PA flow setpoint engaged: VFD adjusts to hold ~7 kg/s ✓
- [ ] Temperature setpoint 75°C: heater modulates smoothly ✓
- [ ] No oscillation in either loop ✓
- [ ] Load table verified: 50% furnace load → 20 kg/s coal demand
**Day 3: Full-Load Validation**
- [ ] 100% load: PA flow = 60 kg/s held ±3% ✓
- [ ] Outlet temperature 75°C ±2°C stable ✓
- [ ] Fineness from mill analyzer: 2000–2500 Blaine (good grind) ✓
- [ ] 4-hour stability run: zero coal blockage events ✓
---
## 📊 Expected Performance (50% Load, Optimal)
| Parameter | Target | Range | Typical |
|-----------|--------|-------|---------|
| **PA Flow** | 60 kg/s | 58–62 kg/s | **60.2 kg/s** |
| **Outlet Temp** | 75°C | 73–77°C | **74.5°C** |
| **Mill Vibration** | <3 mm/s | <5 mm/s | **2.3 mm/s** |
| **Motor Current** | 350 A | <450 A | **385 A** |
| **Coal Fineness** | 2300 Blaine | 2000–2600 | **2350** |
| **Mill Health** | 95/100 | >80/100 | **95** |
---
## 📄 Document Version History
| Version | Date | Author | Change |
|---------|------|--------|--------|
| 1.0 | 2026-04-13 | Claude | Initial template: Load-scheduled PA flow + duct heater temperature control |
---