Structured Text (ST) Programming — Engineering Guide
Shared by TSIMEREZIVO Team · 4 Oct 2026 · 51 views
#
Structured Text (ST) Programming
Structured Text is the most powerful and expressive IEC 61131-3 language —
Pascal-like syntax with rich data types, loops, and function blocks. Ideal for
complex mathematical algorithms, recipe handling, and array processing.
This guide takes you from syntax basics to a working PID function block.
30 min
## ST Syntax Basics
```iecst
(* Variable declarations — in VAR block *)
VAR
blink_state : BOOL := FALSE; (* Output state *)
blink_timer : TON; (* On-delay timer instance *)
blink_period_ms : TIME := T#500ms; (* 500ms half-period *)
END_VAR
(* Program body — executes every scan *)
blink_timer(IN := NOT blink_state, PT := blink_period_ms);
IF blink_timer.Q THEN
blink_state := NOT blink_state; (* Toggle *)
blink_timer(IN := FALSE); (* Reset timer *)
END_IF;
DIGITAL_OUT_01 := blink_state; (* Write to tag *)
```
## Variable Declarations
```iecst
(* --- VAR block types in IEC 61131-3 --- *)
VAR (* Local — per scan cycle, NOT retained *)
setpoint : REAL;
error : REAL;
output : REAL;
END_VAR
VAR_RETAIN (* Retained — survives power cycle *)
total_runtime : DINT; (* Accumulated seconds *)
batch_count : INT;
END_VAR
VAR_INPUT (* Read from external scope / caller *)
pv_scaled : REAL; (* Process variable from AI module *)
sp_from_hmi : REAL; (* Setpoint from operator HMI *)
END_VAR
VAR_OUTPUT (* Written to external scope / caller *)
cv_to_valve : REAL; (* Control variable to AO module *)
in_alarm : BOOL; (* Alarm flag to HMI *)
END_VAR
VAR_IN_OUT (* Read/write pass-through — avoid unless necessary *)
recipe_step : INT;
END_VAR
VAR CONSTANT (* Compile-time constants — never written at runtime *)
MAX_FLOW : REAL := 1000.0; (* L/min *)
MIN_FLOW : REAL := 0.0;
SCAN_MS : REAL := 0.1; (* 100ms scan = 0.1s *)
END_VAR
```
## Control Flow
```iecst
IF temperature > 350.0 THEN
alarm_hihi := TRUE;
output := 0.0; (* Shut down *)
ELSIF temperature > 300.0 THEN
alarm_hi := TRUE;
ELSE
alarm_hi := FALSE;
alarm_hihi := FALSE;
END_IF;
```
```iecst
CASE operating_mode OF
0: (* STOPPED *)
motor_out := FALSE;
valve_cmd := FALSE;
1: (* STARTING *)
motor_out := TRUE;
start_tmr(IN:=TRUE, PT:=T#3s);
IF start_tmr.Q THEN
operating_mode := 2;
END_IF;
2: (* RUNNING *)
motor_out := TRUE;
3: (* FAULT *)
motor_out := FALSE;
fault_latch := TRUE;
ELSE
operating_mode := 0;
END_CASE;
```
```iecst
(* Sum all 16 temperature sensors *)
VAR
i : INT;
temp_sum : REAL := 0.0;
temp_avg : REAL;
temps : ARRAY[1..16] OF REAL;
END_VAR
temp_sum := 0.0;
FOR i := 1 TO 16 DO
temp_sum := temp_sum + temps[i];
END_FOR;
temp_avg := temp_sum / 16.0;
```
```iecst
{`(* Wait for temperature to stabilise *)
WHILE ABS(pv - setpoint) > 2.0 DO
(* Still settling — don't advance step *)
(* Note: avoid infinite WHILE in PLC! *)
(* Use state machine + scan-based checks *)
EXIT; (* Always EXIT if no real wait *)
END_WHILE;
(* Safe pattern: use a BOOL flag instead *)
IF ABS(pv - setpoint)
## Complete PID Function Block
This is a production-quality ISA-S5.1 standard Proportional-Integral-Derivative function block
with anti-windup, bumpless auto/manual transfer, and output clamping. Use it as-is or adapt it
for your process.
```iecst
{`(*
* TSIMEREZIVO_PID — ISA-compatible PID Function Block
* IEC 61131-3 Structured Text
* Anti-windup, bumpless A/M, output clamp
*)
FUNCTION_BLOCK TSIMEREZIVO_PID
VAR_INPUT
PV : REAL; (* Process Variable — scaled EU *)
SP : REAL; (* Setpoint — scaled EU *)
AUTO_MODE : BOOL := TRUE; (* TRUE = Automatic, FALSE = Manual *)
MAN_OUT : REAL := 0.0; (* Manual output (0–100%) *)
Kp : REAL := 1.0; (* Proportional gain *)
Ki : REAL := 0.1; (* Integral gain (1/Ti) *)
Kd : REAL := 0.05; (* Derivative gain *)
OUT_LO : REAL := 0.0; (* Output clamp low (%) *)
OUT_HI : REAL := 100.0; (* Output clamp high (%) *)
SCAN_TIME : REAL := 0.1; (* Scan period in seconds *)
END_VAR
VAR_OUTPUT
OUT : REAL; (* Control variable output 0–100% *)
ERROR : REAL; (* Current error = SP - PV *)
IN_AUTO : BOOL; (* Status: in automatic mode *)
SATURATED : BOOL; (* Output at limit — anti-windup active *)
END_VAR
VAR
integral : REAL := 0.0; (* Integral accumulator *)
prev_error : REAL := 0.0; (* Previous error for derivative *)
p_term : REAL;
i_term : REAL;
d_term : REAL;
out_raw : REAL;
END_VAR
(* --- PID Body --- *)
IN_AUTO := AUTO_MODE;
ERROR := SP - PV;
IF AUTO_MODE THEN
(* P term *)
p_term := Kp * ERROR;
(* I term with anti-windup: freeze integration when output saturated *)
IF NOT SATURATED THEN
integral := integral + (Ki * ERROR * SCAN_TIME);
END_IF;
i_term := integral;
(* D term — derivative on measurement, not error, to prevent setpoint kick *)
d_term := Kd * (prev_error - ERROR) / SCAN_TIME;
out_raw := p_term + i_term + d_term;
(* Output clamp *)
IF out_raw >= OUT_HI THEN
OUT := OUT_HI;
SATURATED := TRUE;
ELSIF out_raw **Tuning PID in LogicForge** —
Use the TSIMEREZIVO built-in step-response tuning wizard: Tags → PID Tuning. It applies a
step change to the output, records the response curve, and calculates initial Kp, Ki, Kd
using Ziegler-Nichols or Cohen-Coon methods. Always verify tuning in Simulator before applying to live plant.