I/O Schedule Template
Shared by TSIMEREZIVO Team · 4 Oct 2026 · 44 views
# I/O Schedule Template
Maps every field signal to a controller channel. The master reference for wiring, marshalling, and program development.
| Field | Description | Example |
|---|---|---|
| I/O Tag | Signal tag | FT-101_PV |
| Service | What it serves | Feedwater flow PV |
| Signal Type | AI/AO/DI/DO/RTD/TC/HART | AI |
| Range / State | Eng range or ON/OFF | 0–250 kg/h |
| System / PLC | Controller | S7-1516-3PN |
| Rack / Slot / Channel | Hardware address | R0/S4/CH3 |
| Terminal / TB | Marshalling terminal | TB1-14/15 |
| Cable / Pair | Field cable | C-1001/P7 |
| Field Device | Source instrument | FT-101 |
| Module Type | Card model | AI 8xU/I HF |
| Fused / Isolated | Barrier or fuse ref | Iso barrier MTL5046 |
| Spare | Y/N | N |
| Remarks | Notes | 4–20mA, loop-powered |
## Rules of thumb
- Reserve ~15% spare channels per rack for future expansion.
- Keep safety and non-safety I/O on separate cards.
- Every wire lands somewhere — no unallocated pairs at punch time.
- Cross-check against the instrument index before FAT.