Instrument Hook-Up Detail Template
Shared by TSIMEREZIVO Team · 4 Oct 2026 · 41 views
# Instrument Hook-Up / Installation Detail Template
Standard installation detail — one per instrument type per service class.
Reference on the instrument index; draw once, reuse everywhere.
## Header block
- Detail No: HK-____ Rev: __
- Instrument type: ______________ (e.g. DP flow transmitter)
- Service class: general / steam / corrosive / IS hazardous (zone: ___)
- Drawing reference standard: ISA / project std
## Typical detail contents (fill per install)
| Item | Material / spec | Qty | Notes |
|---|---|---|---|
| Root isolation valve | 1/2" ball valve, 316SS, 600# | 2 | Primary + secondary |
| Impulse line | 1/2" OD 316SS seamless tube | as req'd | Slope 1:12 min toward process |
| Manifold | 3-valve, 316SS | 1 | Vent to safe location |
| Transmitter | Per datasheet | 1 | Mount below tapping for liquid |
| Mounting | 2" pipe stand, galvanised | 1 | |
| Cable gland | M20 Exd, brass nickel-plated | 1 | |
| Junction | Per cable schedule | — | |
## Rules that prevent rework
- Liquid service: taps horizontal or below — never top-dead-center (gas pockets).
- Gas service: taps top or side — condensate drains away from the transmitter.
- Steam: pigtail siphon + water fill before connecting transmitter.
- Impulse lines >15 m or on viscous service → consider remote seals.
- Every vent/drain needs a plug or valve — never open-ended.
## Inspection points
- [ ] Impulse line slope and support spacing
- [ ] Gland matches cable OD and Ex rating for the zone
- [ ] Tag plate attached and legible
- [ ] Siphon/manifold orientation correct