Aquaculture System — PLC Control Template
Shared by TSIMEREZIVO Team · 4 Oct 2026 · 36 views
# Aquaculture System — Usage Guide
## Overview
Aquaculture support template that supervises dissolved oxygen, temperature, pH, and feed dosing. It is intended for tank-based fish production or hatchery support systems.
## Commissioning
1. Verify DO, pH, and temperature probe calibration before enabling automatic actions
2. Test aerator and cooling outputs independently
3. Validate feed schedule timing and duration against species feeding plan
---
## Control Logic — Vendor-Agnostic Pseudocode
# Aquaculture System — Logic
## Standards: IEC 61131-3 | ISA-5.1 | ISA-18.2
## Scan Rate: 500ms | Pattern: dissolved oxygen, feed dosing, temperature and pH supervision
```
ROUTINE: AquacultureSystem
SCAN_RATE: 500ms
// SECTION 1 — CORE ENVIRONMENTAL CONTROL
IF DO_PV <= DO_LOW_SP THEN AERATOR_CMD := TRUE END_IF
IF DO_PV >= DO_HIGH_SP THEN AERATOR_CMD := FALSE END_IF
IF TEMP_PV >= TEMP_HIGH_SP THEN COOLING_CMD := TRUE END_IF
IF TEMP_PV <= TEMP_LOW_SP THEN COOLING_CMD := FALSE END_IF
// SECTION 2 — FEED DOSING
IF FEED_TIME_MATCH AND AUTO_MODE THEN
FEEDER_CMD := TRUE
FEED_TMR := FEED_TMR + 1
IF FEED_TMR >= FEED_DURATION_TICKS THEN
FEEDER_CMD := FALSE
FEED_TMR := 0
FEED_COUNT := FEED_COUNT + 1
END_IF
END_IF
// SECTION 3 — WATER QUALITY ALARMS
IF DO_PV <= DO_CRIT_SP THEN SET_ALARM(ALM_DO_CRIT, CRITICAL) END_IF
IF PH_PV <= PH_LOW_SP OR PH_PV >= PH_HIGH_SP THEN SET_ALARM(ALM_PH_OUT, HIGH) END_IF
IF TEMP_PV >= TEMP_HH_SP THEN SET_ALARM(ALM_TEMP_HH, HIGH) END_IF
// SECTION 4 — HMI
HMI_DO := DO_PV
HMI_PH := PH_PV
HMI_TEMP := TEMP_PV
HMI_FEED_COUNT := FEED_COUNT
END_ROUTINE
```
---
## Tag List
```csv
Tag Name,Description,Data Type,Direction,Engineering Unit,Range Min,Range Max,Default Value,Address
AUTO_MODE,Automatic Mode Enable,BOOL,input,,,,TRUE,
DO_PV,Dissolved Oxygen Process Value,REAL,input,mg/L,0,20,7,AI:0:0.0
PH_PV,pH Process Value,REAL,input,pH,0,14,7,AI:0:0.1
TEMP_PV,Water Temperature,REAL,input,°C,0,50,24,AI:0:0.2
DO_LOW_SP,Dissolved Oxygen Start Aeration Setpoint,REAL,internal,mg/L,0,20,5,
DO_HIGH_SP,Dissolved Oxygen Stop Aeration Setpoint,REAL,internal,mg/L,0,20,7,
DO_CRIT_SP,Critical Dissolved Oxygen Setpoint,REAL,internal,mg/L,0,20,3,
PH_LOW_SP,Low pH Setpoint,REAL,internal,pH,0,14,6.5,
PH_HIGH_SP,High pH Setpoint,REAL,internal,pH,0,14,8.5,
TEMP_LOW_SP,Low Temperature Cooling Reset,REAL,internal,°C,0,50,24,
TEMP_HIGH_SP,High Temperature Cooling Start,REAL,internal,°C,0,50,28,
TEMP_HH_SP,High-High Temperature Alarm,REAL,internal,°C,0,50,32,
FEED_TIME_MATCH,Feed Schedule Match,BOOL,input,,,,FALSE,
FEEDER_CMD,Feed Doser Command,BOOL,output,,,,FALSE,DO:1:0.0
AERATOR_CMD,Aerator Command,BOOL,output,,,,FALSE,DO:1:0.1
COOLING_CMD,Cooling Valve/Fan Command,BOOL,output,,,,FALSE,DO:1:0.2
FEED_TMR,Feed Duration Timer,INT,internal,,0,10000,0,
FEED_DURATION_TICKS,Feed Duration (500ms ticks),INT,internal,,0,10000,20,
FEED_COUNT,Completed Feed Events,DINT,internal,,0,999999,0,
ALM_DO_CRIT,Critical Low Dissolved Oxygen Alarm,BOOL,calculated,,,,FALSE,
ALM_PH_OUT,pH Out of Range Alarm,BOOL,calculated,,,,FALSE,
ALM_TEMP_HH,High Temperature Alarm,BOOL,calculated,,,,FALSE,
HMI_DO,HMI: Dissolved Oxygen,REAL,output,mg/L,0,20,7,
HMI_PH,HMI: pH,REAL,output,pH,0,14,7,
HMI_TEMP,HMI: Temperature,REAL,output,°C,0,50,24,
HMI_FEED_COUNT,HMI: Feed Count,DINT,output,,0,999999,0,
```
---
## Alarm Matrix
```csv
Alarm Tag,Condition,Setpoint,Priority,Type,Response,Delay,Auto Acknowledge
ALM_DO_CRIT,DO_PV <= DO_CRIT_SP,3 mg/L,critical,process,Critical oxygen deficiency. Force aeration and escalate immediately.,0s,No
ALM_PH_OUT,PH_PV outside PH_LOW_SP..PH_HIGH_SP,6.5-8.5,high,process,pH outside acceptable range. Check dosing chemistry and bio-load.,5s,No
ALM_TEMP_HH,TEMP_PV >= TEMP_HH_SP,32°C,high,process,Water temperature high. Increase cooling and reduce stocking stress.,5s,No
```