Field fix / guidePLC / HMI Code & LogicVendor-agnostic (IEC 61131-3)Pump Systemsindustrial-automation
Three Input Permissive Pump — PLC Control Template
Shared by TSIMEREZIVO Team · 4 Oct 2026 · 45 views
# Three-Input Permissive Pump Logic — Usage Guide
## Overview
Implements the industry-standard AND-gate permissive pattern with 3 configurable process permissives plus hardwired E-Stop and overload, a 5-bit diagnostic word for HMI display, and individual alarm messages per unsatisfied condition.
Used on: transfer pumps, process feed pumps, any application requiring multiple confirmed conditions before starting.
## Permissive Configuration
| Permissive | Default Condition | Configurable? |
|-----------|-------------------|--------------|
| P1 — Upstream Level | LT_UPSTREAM_PV ≥ 20% | Yes — adjust `UPSTREAM_LEVEL_MIN` |
| P2 — Path Clear | Isolation valve open LS active | Swap for any DO/DI condition |
| P3 — Downstream Capacity | LT_DOWNSTREAM_PV < 85% | Yes — adjust `DOWNSTREAM_LEVEL_MAX` |
| P4 — Overload (hardwired) | NC contact from MCC | Hardwired, not software-adjustable |
| P5 — E-Stop (hardwired) | NC safety relay loop | Hardwired, not software-adjustable |
## PERMISSIVE_WORD Bit Map
| Bit | Weight | Permissive |
|-----|--------|-----------|
| 0 | 1 | P1 Upstream Level |
| 1 | 2 | P2 Path Clear |
| 2 | 4 | P3 Downstream Capacity |
| 3 | 8 | P4 Overload OK |
| 4 | 16 | P5 E-Stop OK |
All 5 = 31 → PERMISSIVES_OK = TRUE
## Adding More Permissives
Extend the pattern: add PERM_RAW[3], a new DB_CTR[3], set PERMISSIVE_WORD bit 5, and update the master gate to check bit 5 (PERMISSIVE_WORD = 63 for 6 permissives).
## Commissioning
- Force each permissive condition false one at a time; confirm pump cannot start
- Verify individual alarm messages appear on HMI for each failure
- Check PERMISSIVE_WORD register via HMI — should show which bits are missing
- Test discrepancy alarm by disconnecting feedback wire
---
## Control Logic — Vendor-Agnostic Pseudocode
# Three-Input Permissive Pump Logic — Logic
## Standards: IEC 61131-3 | ISA-5.1 | IEC 61508 SIL1
## Scan Rate: 10ms | Pattern: AND-gate permissive with individual diagnostics
```
ROUTINE: ThreeInputPermissivePump
SCAN_RATE: 10ms
// ═══════════════════════════════════════════════════════════════
// SECTION 1 — INPUT CONDITIONING
// Each permissive input is debounced and individually alarmed.
// This pattern is used in TIA Portal as a network-per-permissive
// style with explicit status bits for HMI display.
// ═══════════════════════════════════════════════════════════════
// Debounce all 3 permissive inputs (20ms)
FOR i := 0 TO 2 DO
IF PERM_RAW[i] THEN
DB_CTR[i] := MIN(DB_CTR[i] + 1, 3)
ELSE
DB_CTR[i] := MAX(DB_CTR[i] - 1, 0)
END_IF
PERM_DB[i] := (DB_CTR[i] >= 2)
END_FOR
// ═══════════════════════════════════════════════════════════════
// SECTION 2 — PERMISSIVE CONDITION DEFINITIONS
// P1: Upstream vessel has adequate level (min fill before pumping)
// P2: Flow path clear (manual isolation valve position confirmed)
// P3: Receiving vessel has capacity (not high-high)
// ═══════════════════════════════════════════════════════════════
// P1: Upstream level adequate (≥ LOW_LEVEL_SETPOINT)
PERM_1_UPSTREAM_LEVEL := (LT_UPSTREAM_PV >= UPSTREAM_LEVEL_MIN)
PERM_1_ACTIVE := PERM_DB[0] AND PERM_1_UPSTREAM_LEVEL
// P2: Flow path confirmed clear
PERM_2_PATH_CLEAR := (XV_ISOLATION_OPEN_LS AND NOT XV_ISOLATION_CLOSED_LS)
PERM_2_ACTIVE := PERM_DB[1] AND PERM_2_PATH_CLEAR
// P3: Downstream vessel has capacity (level < HH setpoint)
PERM_3_DOWNSTREAM_CAP := (LT_DOWNSTREAM_PV < DOWNSTREAM_LEVEL_MAX)
PERM_3_ACTIVE := PERM_DB[2] AND PERM_3_DOWNSTREAM_CAP
// ═══════════════════════════════════════════════════════════════
// SECTION 3 — MASTER PERMISSIVE GATE
// All three permissives AND'ed. Individual failures alarmed.
// Provides 8-state diagnostic word for HMI bit-masking.
// ═══════════════════════════════════════════════════════════════
PERMISSIVE_WORD := 0
IF PERM_1_ACTIVE THEN PERMISSIVE_WORD := PERMISSIVE_WORD OR 1 END_IF
IF PERM_2_ACTIVE THEN PERMISSIVE_WORD := PERMISSIVE_WORD OR 2 END_IF
IF PERM_3_ACTIVE THEN PERMISSIVE_WORD := PERMISSIVE_WORD OR 4 END_IF
IF PERM_OL_OK THEN PERMISSIVE_WORD := PERMISSIVE_WORD OR 8 END_IF
IF PERM_ESTOP_OK THEN PERMISSIVE_WORD := PERMISSIVE_WORD OR 16 END_IF
// All 5 conditions required (3 process + OL + E-Stop)
PERMISSIVES_OK := (PERMISSIVE_WORD = 31) // 0b11111
// ═══════════════════════════════════════════════════════════════
// SECTION 4 — PUMP CONTROL WITH PERMISSIVE GATE
// Start is gated through permissive AND gate.
// Any permissive loss during run → latched stop (requires reset).
// ═══════════════════════════════════════════════════════════════
CASE MODE_SELECTOR OF
0: PUMP_CMD := FALSE; PUMP_LATCH := FALSE
1: // MANUAL
IF PB_START AND PERMISSIVES_OK THEN
PUMP_LATCH := TRUE
END_IF
IF PB_STOP OR NOT PERMISSIVES_OK THEN
PUMP_LATCH := FALSE
END_IF
PUMP_CMD := PUMP_LATCH
2: // AUTO
IF AUTO_START AND PERMISSIVES_OK THEN
PUMP_LATCH := TRUE
END_IF
IF AUTO_STOP OR PB_STOP OR NOT PERMISSIVES_OK THEN
PUMP_LATCH := FALSE
END_IF
PUMP_CMD := PUMP_LATCH
END_CASE
// ═══════════════════════════════════════════════════════════════
// SECTION 5 — PERMISSIVE FAILURE DIAGNOSTICS
// Individual alarms for each unsatisfied permissive.
// HMI word enables single-screen diagnosis.
// ═══════════════════════════════════════════════════════════════
IF NOT PERM_1_ACTIVE THEN
SET_ALARM(ALM_PERM1_FAIL, MEDIUM,
MSG="Upstream level too low — min level not reached")
END_IF
IF NOT PERM_2_ACTIVE THEN
SET_ALARM(ALM_PERM2_FAIL, MEDIUM,
MSG="Flow path not clear — check isolation valve XV")
END_IF
IF NOT PERM_3_ACTIVE THEN
SET_ALARM(ALM_PERM3_FAIL, MEDIUM,
MSG="Downstream vessel full — no capacity for transfer")
END_IF
IF NOT PERM_OL_OK THEN
SET_ALARM(ALM_OVERLOAD, HIGH,
MSG="Motor overload relay tripped")
END_IF
IF NOT PERM_ESTOP_OK THEN
SET_ALARM(ALM_ESTOP, CRITICAL,
MSG="E-Stop active — check safety circuit")
END_IF
// Discrepancy check
IF PUMP_CMD <> PUMP_RUN_FB THEN
DISC_TMR := DISC_TMR + 1
IF DISC_TMR >= 300 THEN
SET_ALARM(ALM_DISCREPANCY, MEDIUM)
END_IF
ELSE
DISC_TMR := 0
END_IF
// ═══════════════════════════════════════════════════════════════
// SECTION 6 — HMI OUTPUTS
// ═══════════════════════════════════════════════════════════════
HMI_PERMISSIVE_WORD := PERMISSIVE_WORD
HMI_PERMISSIVES_OK := PERMISSIVES_OK
HMI_PUMP_RUNNING := PUMP_RUN_FB
HMI_PUMP_CMD := PUMP_CMD
HMI_PERM1_STATE := PERM_1_ACTIVE
HMI_PERM2_STATE := PERM_2_ACTIVE
HMI_PERM3_STATE := PERM_3_ACTIVE
HMI_UPSTREAM_LEVEL := LT_UPSTREAM_PV
HMI_DOWNSTREAM_LEVEL := LT_DOWNSTREAM_PV
HMI_MODE := MODE_SELECTOR
END_ROUTINE
```
---
## Tag List
```csv
Tag Name,Description,Data Type,Direction,Engineering Unit,Range Min,Range Max,Default Value,Address
PERM_RAW_0,Permissive 1 Raw Input,BOOL,input,,,,FALSE,DI:0:0.0
PERM_RAW_1,Permissive 2 Raw Input,BOOL,input,,,,FALSE,DI:0:0.1
PERM_RAW_2,Permissive 3 Raw Input,BOOL,input,,,,FALSE,DI:0:0.2
DB_CTR_0,Permissive 1 Debounce Counter,INT,internal,,0,3,0,
DB_CTR_1,Permissive 2 Debounce Counter,INT,internal,,0,3,0,
DB_CTR_2,Permissive 3 Debounce Counter,INT,internal,,0,3,0,
PERM_DB_0,Permissive 1 Debounced State,BOOL,calculated,,,,FALSE,
PERM_DB_1,Permissive 2 Debounced State,BOOL,calculated,,,,FALSE,
PERM_DB_2,Permissive 3 Debounced State,BOOL,calculated,,,,FALSE,
LT_UPSTREAM_PV,Upstream Vessel Level,REAL,input,%,0,100,,AI:2:0.0
LT_DOWNSTREAM_PV,Downstream Vessel Level,REAL,input,%,0,100,,AI:2:0.1
XV_ISOLATION_OPEN_LS,Isolation Valve Open Limit Switch,BOOL,input,,,,FALSE,DI:0:0.3
XV_ISOLATION_CLOSED_LS,Isolation Valve Closed Limit Switch,BOOL,input,,,,FALSE,DI:0:0.4
UPSTREAM_LEVEL_MIN,Upstream Level Minimum Permissive,REAL,internal,%,0,100,20,
DOWNSTREAM_LEVEL_MAX,Downstream Level Maximum Permissive,REAL,internal,%,0,100,85,
PERM_1_UPSTREAM_LEVEL,P1: Upstream Level Condition Met,BOOL,calculated,,,,FALSE,
PERM_1_ACTIVE,P1: Permissive 1 Satisfied (debounced),BOOL,calculated,,,,FALSE,
PERM_2_PATH_CLEAR,P2: Flow Path Clear Condition,BOOL,calculated,,,,FALSE,
PERM_2_ACTIVE,P2: Permissive 2 Satisfied (debounced),BOOL,calculated,,,,FALSE,
PERM_3_DOWNSTREAM_CAP,P3: Downstream Capacity Condition,BOOL,calculated,,,,FALSE,
PERM_3_ACTIVE,P3: Permissive 3 Satisfied (debounced),BOOL,calculated,,,,FALSE,
PERM_OL_OK,Motor Overload Relay Healthy (NC),BOOL,input,,,,TRUE,DI:0:0.5
PERM_ESTOP_OK,E-Stop Circuit Healthy (NC),BOOL,input,,,,TRUE,DI:0:0.6
PERMISSIVE_WORD,Permissive Status Bitmask (5-bit),INT,calculated,,0,31,0,
PERMISSIVES_OK,All Permissives Satisfied (PERMISSIVE_WORD=31),BOOL,calculated,,,,FALSE,
MODE_SELECTOR,Operating Mode (0=OFF 1=MAN 2=AUTO),INT,input,,0,2,1,
PB_START,Start Pushbutton,BOOL,input,,,,FALSE,DI:0:0.7
PB_STOP,Stop Pushbutton (debounced NC),BOOL,input,,,,FALSE,DI:0:0.8
AUTO_START,Auto Start Command from Process,BOOL,input,,,,FALSE,
AUTO_STOP,Auto Stop Command from Process,BOOL,input,,,,FALSE,
PUMP_CMD,Pump Command Output,BOOL,output,,,,FALSE,DO:1:0.0
PUMP_RUN_FB,Pump Running Feedback,BOOL,input,,,,FALSE,DI:0:0.9
PUMP_LATCH,Pump Latch (Seal-In),BOOL,internal,,,,FALSE,
DISC_TMR,Command/Feedback Discrepancy Timer,INT,internal,,0,500,0,
ALM_PERM1_FAIL,Permissive 1 Not Satisfied — Upstream Level,BOOL,calculated,,,,FALSE,
ALM_PERM2_FAIL,Permissive 2 Not Satisfied — Path Not Clear,BOOL,calculated,,,,FALSE,
ALM_PERM3_FAIL,Permissive 3 Not Satisfied — Downstream Full,BOOL,calculated,,,,FALSE,
ALM_OVERLOAD,Motor Overload Relay Alarm,BOOL,calculated,,,,FALSE,
ALM_ESTOP,E-Stop Active Alarm,BOOL,calculated,,,,FALSE,
ALM_DISCREPANCY,Command/Feedback Discrepancy Alarm,BOOL,calculated,,,,FALSE,
HMI_PERMISSIVE_WORD,HMI: Permissive Status Word,INT,output,,0,31,0,
HMI_PERMISSIVES_OK,HMI: All Permissives OK Flag,BOOL,output,,,,FALSE,
HMI_PUMP_RUNNING,HMI: Pump Running State,BOOL,output,,,,FALSE,
HMI_PUMP_CMD,HMI: Pump Command State,BOOL,output,,,,FALSE,
HMI_PERM1_STATE,HMI: Permissive 1 State,BOOL,output,,,,FALSE,
HMI_PERM2_STATE,HMI: Permissive 2 State,BOOL,output,,,,FALSE,
HMI_PERM3_STATE,HMI: Permissive 3 State,BOOL,output,,,,FALSE,
HMI_UPSTREAM_LEVEL,HMI: Upstream Level Display,REAL,output,%,0,100,,
HMI_DOWNSTREAM_LEVEL,HMI: Downstream Level Display,REAL,output,%,0,100,,
HMI_MODE,HMI: Operating Mode,INT,output,,0,2,1,
```
---
## Alarm Matrix
```csv
Alarm Tag,Condition,Setpoint,Priority,Type,Response,Delay,Auto Acknowledge
ALM_ESTOP,PERM_ESTOP_OK = FALSE,N/A,critical,safety,E-Stop activated. Verify safety of area before clearing. Check safety relay wiring.,0s,No
ALM_OVERLOAD,PERM_OL_OK = FALSE,N/A,high,equipment,Motor thermal overload. Allow cooling before reset. Investigate overload cause.,0s,No
ALM_PERM1_FAIL,PERM_1_ACTIVE = FALSE,20%,medium,process,Upstream level below minimum. Refill upstream vessel or reduce setpoint.,2s,Yes
ALM_PERM2_FAIL,PERM_2_ACTIVE = FALSE,N/A,medium,process,Isolation valve not confirmed open or valve discrepancy. Check valve and limit switches.,2s,Yes
ALM_PERM3_FAIL,PERM_3_ACTIVE = FALSE,85%,medium,process,Downstream vessel at capacity. Reduce downstream demand or increase HH setpoint.,2s,Yes
ALM_DISCREPANCY,PUMP_CMD != PUMP_RUN_FB for >3s,3s,medium,equipment,Output commanded but motor feedback disagrees. Check MCC, contactor, and wiring.,3s,Yes
```