Smart Street Lighting — PLC Control Template
Shared by TSIMEREZIVO Team · 4 Oct 2026 · 51 views
# Smart Street Lighting — Usage Guide
## Overview
Adaptive street lighting template using ambient lux and occupancy boost dimming.
## Commissioning
1. Verify lux sensor orientation and shielding from direct luminaire glare
2. Set dusk and dawn thresholds with adequate hysteresis
3. Test occupancy boost and lamp-fault indication at night conditions
---
## Control Logic — Vendor-Agnostic Pseudocode
# Smart Street Lighting — Logic
## Standards: IEC 61131-3
## Scan Rate: 1s | Pattern: dusk-to-dawn with occupancy boost
```
ROUTINE: SmartStreetLighting
SCAN_RATE: 1s
LIGHTS_ON := LUX_PV <= LUX_ON_SP
IF LUX_PV >= LUX_OFF_SP THEN LIGHTS_ON := FALSE END_IF
IF LIGHTS_ON THEN
DIM_LEVEL := BASE_DIM_PCT
IF MOTION_DETECTED THEN DIM_LEVEL := BOOST_DIM_PCT END_IF
ELSE
DIM_LEVEL := 0.0
END_IF
IF LAMP_FAULT THEN SET_ALARM(ALM_LAMP_FAULT, HIGH) END_IF
HMI_DIM_LEVEL := DIM_LEVEL
END_ROUTINE
```
---
## Tag List
```csv
Tag Name,Description,Data Type,Direction,Engineering Unit,Range Min,Range Max,Default Value,Address
LUX_PV,Ambient Light Level,REAL,input,lux,0,200000,0,AI:0:0.0
MOTION_DETECTED,Motion Detection Input,BOOL,input,,,,FALSE,DI:0:0.0
LAMP_FAULT,Lamp Fault Input,BOOL,input,,,,FALSE,DI:0:0.1
LUX_ON_SP,Dusk Switch-On Threshold,REAL,internal,lux,0,200000,50,
LUX_OFF_SP,Dawn Switch-Off Threshold,REAL,internal,lux,0,200000,100,
BASE_DIM_PCT,Base Night Dim Level,REAL,internal,%,0,100,40,
BOOST_DIM_PCT,Occupied Boost Dim Level,REAL,internal,%,0,100,100,
LIGHTS_ON,Lights On State,BOOL,calculated,,,,FALSE,
DIM_LEVEL,Lighting Dim Level,REAL,output,%,0,100,0,
ALM_LAMP_FAULT,Lamp Fault Alarm,BOOL,calculated,,,,FALSE,
HMI_DIM_LEVEL,HMI: Dim Level,REAL,output,%,0,100,0,
```
---
## Alarm Matrix
```csv
Alarm Tag,Condition,Setpoint,Priority,Type,Response,Delay,Auto Acknowledge
ALM_LAMP_FAULT,LAMP_FAULT = TRUE,N/A,high,equipment,Lighting circuit fault detected. Inspect luminaire and driver.,0s,No
```