Dam Gate 5 Alarm Levels — PLC Control Template
Shared by TSIMEREZIVO Team · 4 Oct 2026 · 37 views
# Dam Gate 5 Alarm Levels — Usage Guide
## Overview
Flood-management template with five escalating alarm levels and corresponding gate position commands. Designed for reservoir outlet gates, spillway control, and storm-water retention systems where simple, deterministic staged response is preferred.
## Stage Map
| Stage | Threshold | Gate Command | Meaning |
|------|-----------|--------------|---------|
| 0 | below `SP_STAGE1` | 0% | Normal |
| 1 | `SP_STAGE1` | 20% | Advisory |
| 2 | `SP_STAGE2` | 40% | Flood watch |
| 3 | `SP_STAGE3` | 60% | Flood warning |
| 4 | `SP_STAGE4` | 80% | Severe flood warning |
| 5 | `SP_STAGE5` | 100% | Emergency spill |
## Commissioning
1. Verify dam level scaling and sensor redundancy policy
2. Force each stage threshold and confirm matching gate command
3. Check actuator travel time and confirm 0 to 100% command range mapping
4. Review downstream hydraulic capacity before enabling AUTO mode
---
## Control Logic — Vendor-Agnostic Pseudocode
# Dam Gate 5 Alarm Levels — Logic
## Standards: IEC 61131-3 | ISA-5.1 | ISA-18.2
## Scan Rate: 250ms | Pattern: Flood management with 5-stage gate opening
```
ROUTINE: DamGateFiveAlarmLevels
SCAN_RATE: 250ms
// SECTION 1 — LEVEL MEASUREMENT
LT001_MA := SCALE(LT001_RAW, 0, 27648, 4.0, 20.0)
LT001_VALID := (LT001_MA >= 3.8) AND (LT001_MA <= 20.5)
IF LT001_VALID THEN
LEVEL_PV := SCALE(LT001_MA, 4.0, 20.0, 0.0, 100.0)
LEVEL_LAST_GOOD := LEVEL_PV
ELSE
LEVEL_PV := LEVEL_LAST_GOOD
SET_ALARM(ALM_LEVEL_SENSOR_FAIL, HIGH)
END_IF
// SECTION 2 — FIVE-LEVEL FLOOD ALARM STAGING
IF LEVEL_PV >= SP_STAGE5 THEN GATE_STAGE := 5
ELSIF LEVEL_PV >= SP_STAGE4 THEN GATE_STAGE := 4
ELSIF LEVEL_PV >= SP_STAGE3 THEN GATE_STAGE := 3
ELSIF LEVEL_PV >= SP_STAGE2 THEN GATE_STAGE := 2
ELSIF LEVEL_PV >= SP_STAGE1 THEN GATE_STAGE := 1
ELSE GATE_STAGE := 0
END_IF
// SECTION 3 — GATE POSITION COMMANDS
CASE MODE_SELECTOR OF
0: // OFF
GATE_CMD := 0.0
1: // MANUAL
GATE_CMD := MAN_GATE_CMD
2: // AUTO
CASE GATE_STAGE OF
0: GATE_CMD := 0.0
1: GATE_CMD := 20.0
2: GATE_CMD := 40.0
3: GATE_CMD := 60.0
4: GATE_CMD := 80.0
5: GATE_CMD := 100.0
END_CASE
END_CASE
// SECTION 4 — FLOOD ALARMS
IF GATE_STAGE >= 1 THEN SET_ALARM(ALM_STAGE1, LOW) END_IF
IF GATE_STAGE >= 2 THEN SET_ALARM(ALM_STAGE2, MEDIUM) END_IF
IF GATE_STAGE >= 3 THEN SET_ALARM(ALM_STAGE3, HIGH) END_IF
IF GATE_STAGE >= 4 THEN SET_ALARM(ALM_STAGE4, HIGH) END_IF
IF GATE_STAGE >= 5 THEN SET_ALARM(ALM_STAGE5, CRITICAL) END_IF
// SECTION 5 — HMI OUTPUTS
HMI_LEVEL_PV := LEVEL_PV
HMI_GATE_STAGE := GATE_STAGE
HMI_GATE_CMD := GATE_CMD
HMI_MODE := MODE_SELECTOR
END_ROUTINE
```
---
## Tag List
```csv
Tag Name,Description,Data Type,Direction,Engineering Unit,Range Min,Range Max,Default Value,Address
LT001_RAW,Dam Level Transmitter Raw ADC,INT,input,,0,27648,,AI:0:0.0
LT001_MA,Dam Level mA,REAL,calculated,mA,3.8,20.5,,
LT001_VALID,Dam Level Transmitter Healthy,BOOL,calculated,,,,TRUE,
LEVEL_PV,Dam Level Process Value,REAL,calculated,%,0,100,,
LEVEL_LAST_GOOD,Last Good Dam Level,REAL,internal,%,0,100,50,
MODE_SELECTOR,Operating Mode (0=OFF 1=MAN 2=AUTO),INT,input,,0,2,2,
MAN_GATE_CMD,Manual Gate Position Command,REAL,input,%,0,100,0,
GATE_STAGE,Active Flood Stage,INT,calculated,,0,5,0,
GATE_CMD,Gate Position Command,REAL,output,%,0,100,0,
SP_STAGE1,Stage 1 Flood Threshold,REAL,internal,%,0,100,60,
SP_STAGE2,Stage 2 Flood Threshold,REAL,internal,%,0,100,70,
SP_STAGE3,Stage 3 Flood Threshold,REAL,internal,%,0,100,80,
SP_STAGE4,Stage 4 Flood Threshold,REAL,internal,%,0,100,90,
SP_STAGE5,Stage 5 Flood Threshold,REAL,internal,%,0,100,97,
ALM_LEVEL_SENSOR_FAIL,Dam Level Sensor Failure,BOOL,calculated,,,,FALSE,
ALM_STAGE1,Stage 1 Flood Advisory,BOOL,calculated,,,,FALSE,
ALM_STAGE2,Stage 2 Flood Watch,BOOL,calculated,,,,FALSE,
ALM_STAGE3,Stage 3 Flood Warning,BOOL,calculated,,,,FALSE,
ALM_STAGE4,Stage 4 Severe Flood Warning,BOOL,calculated,,,,FALSE,
ALM_STAGE5,Stage 5 Emergency Spill Condition,BOOL,calculated,,,,FALSE,
HMI_LEVEL_PV,HMI: Dam Level PV,REAL,output,%,0,100,,
HMI_GATE_STAGE,HMI: Flood Stage,INT,output,,0,5,0,
HMI_GATE_CMD,HMI: Gate Command,REAL,output,%,0,100,0,
HMI_MODE,HMI: Operating Mode,INT,output,,0,2,2,
```
---
## Alarm Matrix
```csv
Alarm Tag,Condition,Setpoint,Priority,Type,Response,Delay,Auto Acknowledge
ALM_LEVEL_SENSOR_FAIL,LT001_VALID = FALSE,wire-break,high,equipment,Level transmitter fault. Verify redundant gauging before operating gates automatically.,5s,No
ALM_STAGE1,LEVEL_PV >= SP_STAGE1,60%,low,process,Stage 1 advisory. Prepare operators and inspect outflow channel.,10s,Yes
ALM_STAGE2,LEVEL_PV >= SP_STAGE2,70%,medium,process,Stage 2 flood watch. Increase supervision and confirm gate availability.,5s,No
ALM_STAGE3,LEVEL_PV >= SP_STAGE3,80%,high,process,Stage 3 flood warning. Confirm gate response and downstream evacuation plans.,3s,No
ALM_STAGE4,LEVEL_PV >= SP_STAGE4,90%,high,process,Stage 4 severe flood condition. Maximum response readiness required.,1s,No
ALM_STAGE5,LEVEL_PV >= SP_STAGE5,97%,critical,safety,Emergency spill condition. Command full gate opening and escalate immediately.,0s,No
```